The detector indicates fire hazards using the built-in LED indicator and alarm outputs ALARM and TAMPER. These outputs must be connected to control panels complying with EN 50131-3.
The SD-282 ST consists of two independent detectors – an optical smoke detector and a heat detector. The optical smoke detector works on the principle of scattered light and is very sensitive to dust particles which are present in smoke. There is also a built-in heat detector for detecting fire which generates heat quickly with a small amount of smoke. The microprocessor performs digital analysis for a high false-alarm immunity.
Power | 9 - 15V DC / 5 mA |
---|---|
Smoke detection | optical light scattering |
Smoke detector sensitivity | m = 0.11 - 0.13 dB/m pursuant to EN 54-7 |
Heat detection | class A2 according to EN 54-5 |
Alarm temperature | + 60°C to + 70°C |
Operating temperature range | -10 to +80°C |
Dimensions, weight | diameter 126 mm, height 65 mm, 150 g |
Conformity | EN 54-7, EN 54-5, EN 50130-4, EN 55022 |